Faults / Alarms
05.05
10-10
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
Fault message from free function block FB5
(active in all operating states)
Fault value:
F034
1
the binector wired via parameter U103 Index.001 is in the state log.”1”
2
the binector wired via parameter U103 Index.002 is in the state log.”1”
3
the binector wired via parameter U103 Index.003 is in the state log.”1”
4
the binector wired via parameter U103 Index.004 is in the state log.”1”
10.1.2.7 Drive faults
F035
Drive is blocked
(active in operating states of – –, I, II)
This monitoring function responds if the following conditions are fulfilled for longer than the period set in parameter P355:
♦
Positive or negative torque or armature current limit
♦
The armature current is higher than 1% of the converter rated armature DC current
♦
The actual speed is less than 0.4% of maximum speed
Possible fault causes
♦
Drive is blocked
F036
No armature current is flowing
(active in operating states of – –, I, II)
This monitoring function responds if the armature firing angle is at the rectifier stability limit for more than 500 ms and the
armature current is less than 1% of the converter rated armature DC current.
Possible fault causes
♦
Armature circuit is open
(e.g. DC fuses have blown, open circuit, etc.)
♦
Rectifier stability limit
α
G (P150) is incorrectly set
♦
Drive is operating at
α
G limit (e.g. due to supply undervoltage)
♦
EMF is too high because maximum speed setting is too high,
refer to P083, P115, P143, P741)
♦
EMF is too high because field weakening is not selected (refer to P082)
♦
EMF is too high because field current is set too high (refer to P102)
♦
EMF is too high because transition speed for field weakening is set too high (refer to P101) ??
F037 I2t motor monitor has responded
(active in operating states of – –, I, II)
This monitoring function responds when an I2t value is reached which corresponds to the final temperature at 110% of the rated
motor armature current.
Possible fault causes
♦
Parameter P114 is incorrectly set
♦
Drive has been operating for too long at >110% of rated motor armature current
F038 Overspeed
(active in operating states of – –, I, II)
This fault message is activated if the actual speed value (selected in P595) exceeds the positive (P380) or negative (P381)
threshold by 0.5%.
Possible fault causes
♦
Lower current limit has been input
♦
Current-controlled
operation
♦
P512, P513 are set too low
♦
Tachometer cable contact fault in operation close to maximum speed
F039 I2t power section monitor has responded
(active in operating states of – –, I, II)
This monitoring function responds if the calculated I2t value of the power section reaches the permissible value for the power
section concerned (see also P075).
Possible fault causes
♦
Drive has been operating at overload for too long
♦
Parameter P075 is incorrectly set
♦
Parameter P077 is incorrectly set
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......