Connections
05.05
6-14
Siemens AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
6.1.2.4 List of recommended RI suppression filters made by EPCOS:
Rated current
RI suppression
filter (A)
RI suppression filter
Order number
Terminal
cross-section
(mm²)
Holes for M . .
Weight
(kg)
Dimensions
HxWxD
(mm)
8
B84143-G8-R11*
4 mm²
1,3
80 x 230 x 50
20
B84143-G20-R11*
4 mm²
1,3
80 x 230 x 50
36
B84143-G36-R11*
6 mm²
2,8
150 x 280 x 60
50
B84143-G50-R11*
16 mm²
3,3
150 x 60 x 330
66
B84143-G66-R11*
25 mm²
4,4
150 x 330 x 80
90
B84143-G90-R11*
25 mm²
4,9
150 x 330 x 80
120
B84143-G120-R11*
50 mm²
7,5
200 x 380 x 90
150
B84143-G150-R11*
50 mm²
8,0
200 x 380 x 90
220
B84143-G220-R11*
95 mm²
11,5
220 x 430 x 110
150
B84143-B150-S**
M10
13
140 x 310 x 170
180
B84143-B180-S**
M10
13
140 x 310 x 170
250
B84143-B250-S**
M10
15
115 x 360 x 190
320
B84143-B320-S**
M10
21
115 x 360 x 260
400
B84143-B400-S**
M10
21
115 x 360 x 260
600
B84143-B600-S**
M10
22
115 x 410 x 260
1000
B84143-B1000-S**
M12
28
165 x 420 x 300
1600
B84143-B1600-S**
2 x M12
34
165 x 550 x 300
2500
B84143-B2500-S**
4 x M12
105
200 x 810 x 385
*) The code for the construction type must be inserted instead of *:
0 = 480 V 2 = 530 V
**) The code for the construction type must be inserted instead of **:
20 = 500 V 21 = 760 V 24 = 690 V
*) RI suppression filters produce discharge currents. VDE 0160 stipulates a 10 mm² PE
connection. To ensure an optimum filtering effect, it is absolutely essential to mount the filters and
converter on a single metal plate.
In the case of converters with a 3-phase connection, the minimum rated current of the filter
equals the output DC of the converter times 0.82.
With a two-phase connection (field supply and electronics supply), only two phases are connected
to the three-phase RI suppression filter. In this case, the line current equals the field DC (plus 1A
for the electronics supply).
Important technical data of Siemens RI suppression filters:
Rated supply voltage
3AC 380-460 V (± 15%)
Rated frequency
50/60 Hz (± 6%)
Operating temperature
0
°
C to +40
°
C
Degree of protection
IP20 (EN60529) IP00 with 500 A and above
For further technical data about RI suppression filters, please refer to the Operating Instructions:
SIMOVERT Master Drives RI Suppression Filters EMC Filters, Order number:
6SE7087-6CX87-0FB0.
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......