05.05
Parameter list
SIEMENS AG 6RX1700-0AD76
11-25
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P119
FDS
(G165)
Rated speed
Speed at which an actual EMF value as set in parameter P118 is reached at
full field (according to parameter P102).
This parameter is set automatically during the optimization run for field
weakening (P051=27) and specifies in this case the field-weakening
activation limit speed.
Note:
As regards the closed-loop field-weakening control, only the ratio between
P118 and P119 is relevant. When the setting in P100, P101 or P110 is
changed subsequently, the field-weakening optimization run need not be
repeated. However, P119 then no longer defines the field-weakening
activation limit speed.
When the setting in parameter P102 is changed subsequently, the field-
weakening optimization run must be repeated, the same applies if the
maximum speed setting is subsequently re-adjusted.
0.0 to 199.9
[%]
0.1%
Ind: 4
FS=100.0
Type: O2
P052 = 3
P051 = 40
Offline
Magnetization characteristic (field characteristic)
Parameters P120 to P139 determine the curve shape of the magnetization characteristic (field characteristic) in normalized representation
(see example field characteristic below for further details).
Note:
When the setting in parameter P102 is changed subsequently, the field-weakening optimization run must be repeated, because this alters
the degree of saturation and thus the shape of the magnetization characteristic. (When parameter P100, P101 or P110, or the maximum
speed adjustment, is subsequently altered, the settings in P120 to P139 remain the same, but the values in P118 and/or P119 are
changed).
r120
FDS
(G165)
(G166)
Field current for 0% motor flux (field characteristic, point no. 0)
0.0
[% of P102]
0.1% of P102
Ind: 4
Type: O2
P052 = 3
P121
FDS
(G165)
(G166)
Field current for 5% motor flux (field characteristic, point no. 1)
0.0 to 100.0
[%]
0.1% of P102
Ind: 4
FS=3.7
Type: O2
P052 = 3
P051 = 40
Offline
P122
FDS
(G165)
(G166)
Field current for 10% motor flux (field characteristic, point no. 2)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=7.3
Type: O2
P052 = 3
P051 = 40
Offline
P123
FDS
(G165)
(G166)
Field current for 15% motor flux (field characteristic, point no. 3)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=11.0
Type: O2
P052 = 3
P051 = 40
Offline
P124
FDS
(G165)
(G166)
Field current for 20% motor flux (field characteristic, point no. 4)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=14.7
Type: O2
P052 = 3
P051 = 40
Offline
P125
FDS
(G165)
(G166)
Field current for 25% motor flux (field characteristic, point no. 5)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=18.4
Type: O2
P052 = 3
P051 = 40
Offline
P126
FDS
(G165)
(G166)
Field current for 30% motor flux (field characteristic, point no. 6)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=22.0
Type: O2
P052 = 3
P051 = 40
Offline
P127
FDS
(G165)
(G166)
Field current for 35% motor flux (field characteristic, point no. 7)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=25.7
Type: O2
P052 = 3
P051 = 40
Offline
P128
FDS
(G165)
(G166)
Field current for 40% motor flux (field characteristic, point no. 8)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=29.4
Type: O2
P052 = 3
P051 = 40
Offline
P129
FDS
(G165)
(G166)
Field current for 45% motor flux (field characteristic, point no. 9)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=33.1
Type: O2
P052 = 3
P051 = 40
Offline
P130
FDS
(G165)
(G166)
Field current for 50% motor flux (field characteristic, point no. 10)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=36.8
Type: O2
P052 = 3
P051 = 40
Offline
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......