Faults / Alarms
05.05
10-6
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
10.1.2.2 Interface error
F011
Telegram failure at GSST1
when P780 = 2:
USS telegram failure at G-SST1
(active from the first receipt of a valid protocol in all operating states)
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P787.
Possible fault causes
♦
Cable
break
♦
Error in USS master
F012
Telegram failure at GSST2
when P790 = 2:
USS telegram failure at G-SST2
(active from the first receipt of a valid protocol in all operating states)
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P797.
Possible fault causes
♦
Cable
break
♦
Error in USS master
when P790 = 4 or 5:
Peer-to-peer telegram failure at G-SST2
(active in operating states of
≤
o6)
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P797.
Possible fault causes
♦
Interruption in connecting cable
♦
EMC interference on connecting cable
♦
P797 is set too low
F013
Telegram failure at GSST3
when P800 = 2:
USS telegram failure to G-SST3
(active from the first receipt of a valid protocol in all operating states)
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P807.
Possible fault causes
♦
Cable
break
♦
Error in USS master
when P800 = 4 or 5:
Peer-to-peer telegram failure at G-SST3
(active in operating states of
≤
o6)
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P807.
Possible fault causes
♦
Interruption in connecting cable
♦
EMC interference on connecting cable
♦
P807 is set too low
F014
Telegram failure at paralleling interface
(active when U800 = 1 or 2 from the first receipt of a valid protocol in all operating states)
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter U807.
Possible fault causes
♦
Interruption in connecting cable
♦
EMC interference on connecting cable
♦
U807 is set too low
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......