Start-Up
05.05
7-42
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
When an SLB is employed as the dispatcher, the task table is configured solely on the basis of
drive parameters. The following restrictions apply as compared to the use of a SIMOLINK master
as the dispatcher:
Flexible address lists with gaps in address sequence are not allowed on the bus. Addresses
are assigned consecutively to the nodes, starting with address 0.
The number of telegrams (channels) used per node is identical for all nodes.
It is not possible to use application-specific special data.
All other active bus nodes apart from the dispatcher are
transceivers
. These simply forward
telegrams (with updated contents in some cases) along the bus.
Active
bus nodes receive and/or send telegrams (SIMOLINK master, dispatcher, transceivers).
Passive
bus nodes simply forward received telegrams along the bus without changing their
contents (separating filters, concentrators).
A separate address is assigned to each active bus node; the dispatcher is always assigned node
address 0.
A maximum of 8 telegrams can be transferred per active node. The number of telegrams used per
node is a parameterizable quantity.
Telegrams are identified by the node address and distinguished by their channel number of
between 0 and 7, with 2 data words transferred as user data in each telegram. The first channel
number starts with 0 and is counted in ascending sequence.
Telegram
Word0
Word1
Application Flags
Channel number
Node address
The assignment between connector values to be transferred and individual telegrams and
channels is also parameterized (see Section 8, Sheet Z122).
Transmission of double-word connectors:
The values of double-word connectors can be transmitted in the first four channels (selected with
U749.01 to U749.04 in the receive direction or with U751.01 to U751.08 in the transmission
direction). In the receive direction, the values of any two adjacent connectors (K) are combined to
form a double-word connector (KK) (e.g. K7001 and K7002 to KK7031). These double-word
connectors can be connected to other function blocks in the usual way. For details of how to
connect with double-word connectors, see Section 9.1, subsection, " The following rules apply to
the selection of double-word connectors ".
In the transmission direction, a double-word connector is applied by entering the same double-
word connector at two contiguous indices of selection parameter U751.
Examples:
.04
.01
.03
.02
U751 (0)
9498
9498
401
KK9498
KK9498
K0401
402
K0402
Word
L-Word
Word
H-Word
2x the same KK - number
.04
.01
.03
.02
U751 (0)
9498
9499
401
KK9498
KK9499
K0401
402
K0402
Word
H-Word
Word
H-Word
2 different KKs !
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......