Parameter list
05.05
11-142
SIEMENS AG 6RX1700-0AD76
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
Technology controller: Controller parameters
U488
(2488)
S00
FDS
(B170)
P gain
FB 114
0.10 to 200.00
0.01
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
U489
(2489)
*
S00
(B170)
Source for input quantity (x) for Kp adaptation
FB 114
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U490
(2490)
S00
FDS
(B170)
Characteristic for Kp adaptation: Threshold 1 (x1)
FB 114
0.00 to 200.00
[%]
0.01
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
U491
(2491)
S00
FDS
(B170)
Characteristic for Kp adaptation: Threshold 2 (x2)
FB 114
0.00 to 200.00
[%]
0.01
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
U492
(2492)
S00
FDS
(B170)
Characteristic for Kp adaptation: Minimum value (y1)
FB 114
Minimum value of Kp factor (y) when x
≤
x1
0.10 to 30.00
0.01
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Online
U493
(2493)
S00
FDS
(B170)
Characteristic for Kp adaptation: Maximum value (y2)
FB 114
Maximum value of Kp factor (y) when x
≥
x2
0.10 to 30.00
0.01
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Online
U494
(2494)
S00
FDS
(B170)
Reset time
FB 114
See also U495
0.010 to 60.000
[s]
0.001
Ind: 4
FS=3.000
Type: O2
P052 = 3
P051 = 40
Online
U495
(2495)
*
S00
FDS
(B170)
Factor for reset time
FB 114
0
Reset time = U494 * 1
1
Reset time = U494 * 1000
0 to 1
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
Technology controller: Speed droop
A parameterizable feedback loop can be connected in parallel to the I and P components of the technology controller (acts on summation
point of setpoint and actual value). This loop can be activated and deactivated by settings in parameter U496 (loop can also be
deactivated by setting U497 = 0).
U496
(2496)
*
S00
(B170)
Source for control bit for speed droop injection
FB 114
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U497
(2497)
S00
FDS
(B170)
Speed droop
FB 114
Example:
A 10% speed droop setting causes a 10% reduction in the setpoint at a
100% controller output ("softening" of closed-loop control).
0.0 to 60.0
[%]
0.1
Ind: 4
FS=0.0
Type: O2
P052 = 3
P051 = 40
Online
U498
(2498)
S00
FDS
(B170)
Positive limit for speed droop
FB 114
0.00 to 199.99
[%]
0.01
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
U499
(2499)
S00
FDS
(B170)
Negative limit for speed droop
FB 114
-200.00 to 0.00
[%]
0.01
Ind: 4
FS=-100.00
Type: I2
P052 = 3
P051 = 40
Online
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......