05.05
Faults / Alarms
SIEMENS AG 6RX1700-0AD76
10-7
SIMOREG DC Master Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
F015
Telegram failure on one SIMOLINK board
(active when U741 > 0 as soon as the first valid telegram is received)
After receipt of one valid telegram, no further valid telegrams have arrived within the period set in parameter U741.
Possible fault causes
♦
Break in connecting cable
♦
Parameter setting change during telegram exchange (for parameters see Section 11 "Configuration of SIMOLINK board)
♦
U741 is set to low
Fault value:
1 Telegram failure on 1
st
SLB
2 Reserved
F016
Hardware fault on expansion board EB1
Fault
value:
1
Fault on first EB1
2
Fault on second EB1
F017
Hardware fault on expansion board EB2
Fault
value:
1
Fault on first EB2
2
Fault on second EB2
F018
Short circuit or overloading of binary outputs
(active in all operating states)
Possible fault causes
♦
Short circuit or overload at terminals 46, 48, 50 or 52 and 26 or 34
Fault value:
r047 Index 002 to 016:
1
Short circuit or overload at binary outputs
i002 Bit 8 = 1:
Overload at terminal 46
Bit 9 = 1:
Overload at terminal 48
Bit 10 = 1: Overload at terminal 50
Bit 11 = 1: Overload at terminal 52
Bit 12 = 1: Overload at terminal 26 (15 V output)
Bit 13 = 1: Overload at terminal 34, 44 and/or 210
(24 V output)
NOTICE
This monitoring function is deactivated in the delivery state. It can be activated via parameter P820.
10.1.2.3 External faults
Fault message from free function block FB286
(active in all operating states)
Fault value:
F019
1
the binector wired via parameter U100 Index.005 is in the state log.”1”
2
the binector wired via parameter U100 Index.006 is in the state log.”1”
3
the binector wired via parameter U100 Index.007 is in the state log.”1”
4
the binector wired via parameter U100 Index.008 is in the state log.”1”
Fault message from free function block FB287
(active in all operating states)
Fault value:
F020
1
the binector wired via parameter U101 Index.005 is in the state log.”1”
2
the binector wired via parameter U101 Index.006 is in the state log.”1”
3
the binector wired via parameter U101 Index.007 is in the state log.”1”
4
the binector wired via parameter U101 Index.008 is in the state log.”1”
F021
External fault 1
(active in all operating states)
Bit 15 in control word 1 was in the log. "0" state for longer than the time set in P360 index 001
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......