Faults / Alarms
SIEMENS AG 6RX1700-0AD76
10-15
SIMOREG DC Master Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
14
The speed has changed by more than 12.5% at a constant speed setpoint even through the applied field current setpoint is
still
≥
50% of P102 (IF,motor)
Possible cause: as for fault value 12
15
The EMF setpoint is too small to plot a field characteristic
EMFset = UA – IA,motor * RA = P101 – P100 * P110 < 10% of 1.35 * P078.i001
(e.g. P078.i001 = 400 V . . . minimum EMFset = 54 V)
16
Field weakening operation is not allowed in operation without a tachometer (P083=3)
17
The field current controller cannot be optimized because the field circuit time constant cannot be determined (actual field
current does not decay after switch-off to below 0.95*initial value within approximately 1s or to below 0.8 * 0.95*initial
values within approximately 2 s)
Possible cause:
•
Setting in P103 is too high
•
Field circuit inductance is too high
•
Fault in actual field current sensing circuit (gating board or A7001 electronics board defective)
•
Ratio r073.02 / P102 is too high (change P076.02 if necessary)
18
Field weakening range is too wide, i.e. during power-up (at full field) to a speed setpoint of +10% nmax , the |EMK| is > 77%
of setpoint EMF (P101 – P100 * P110)
Possible cause:
•
Maximum speed setting is incorrect
•
Pulse encoder parameters are incorrect (P140 to P143)
•
Parameters for tachometer adaptation are incorrect (P741)
•
Setpoint EMF is not correct (P101, P100, P110)
•
An excessively high load torque (in positive or negative direction, e.g. a suspended load) causes the drive to rotate, one
of the armature current or torque limits may be parameterized too low
19
A steady-state actual speed of +10%, +20%, +30% . . . or +100% of the maximum speed cannot be reached within 3
minutes (or maximum value of the three set acceleration times) in speed-controlled operation (the speed setpoint/actual
value difference averaged over 90 firing cycles must equal <0.1% nmax
for a specific time period)
Possible cause:
•
Acceleration time is set too low (P303, P307, P311)
•
Drive is blocked
•
An excessively high load torque (in positive or negative direction, e.g. a suspended load) causes the drive to rotate, one
of the armature current or torque limits may be parameterized too low
•
Poor speed controller setting (P225, P226, P228) or speed controller is parameterized as pure P controller or with
droop
•
A band elimination filter (P201, P202 or P203, P204) is active
•
Command “Ramp-function generator enable” =0 or ”Ramp-function generator STOP” =1 is applied
•
“Field weakening operation” (P081 = 1) is not parameterized
20
Current limit is too low
(With speed controller optimization run: Less than 30% or 45% of P100 (IA,motor) + the armature current required for zero
speed,
With optimization run for friction moment and moment of inertia compensation: Less than 20% of P100 (IA, motor) + the
armature current required for a steady-state speed corresponding to 10% of maximum speed)
21
Field weakening range is too wide (nact < +7% nmax
produces |EMF| > 54% setpoint EMF)
(setpoint EMF= K289= P101 – P100 * P110)
Possible cause:
•
Maximum speed setting is incorrect
•
Pulse encoder parameters are incorrect (P140 to P143)
•
Parameters for tachometer adaptation are incorrect (P741)
•
Setpoint EMF is not correct (P101, P100, P110)
•
Caution:
Even a high absolute negative actual speed value can produce an | EMF | of > 54% setpoint EMF
Содержание 6RA7013-6DV62
Страница 10: ...Contents 05 05 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 14: ...Safety Information 01 04 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 58: ...Shipment Unpacking 01 04 4 2 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 158: ...Connections 05 05 6 72 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 648: ...Parameter list 05 05 11 184 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 710: ...Connectors and binectors 05 05 12 62 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 720: ...Maintenance 05 05 13 10 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 726: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 728: ...Applications 01 04 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 730: ...Appendix 05 05 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 732: ...Appendix 05 05 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Страница 733: ......