Settings
46
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
Table 9: Seconds-to-Cycles Conversion (60 Hz)
Seconds Cycles
(50 Hz)
(60 Hz)
Seconds Cycles
(50 Hz)
(60 Hz)
0.3 15 18 15 750 900
0.5 25 30 20 1000
1200
1 50 60 30 1500
1800
2 100
120
45 2250
2700
3 150
180
60 3000
3600
5 250
300
90 4500
5400
7 350
420
120 6000
7200
10 500
600
180 9000
10800
for 50 Hz systems:
_____ seconds x 50 cycles/second
= _____ cycles
_____ minutes x 3000 cycles/minute = _____ cycles
for 60 Hz systems:
_____ seconds x 60 cycles/second
= _____ cycles
_____ minutes x 3600 cycles/minute = _____ cycles
No.
Setting
Default
Range (see Note below)
Incr.
18
Reclose interval 1
300.00
0-999999.00 cycles
0.25 cyc.
19
Reclose interval 2
600.00
0-999999.00 cycles
0.25 cyc.
20
Reclose interval 3
600.00
0-999999.00 cycles
0.25 cyc.
21
Reclose interval 4
0.00
0-999999.00 cycles
0.25 cyc.
The
Reclose interval
settings (1 through 4) are each successively and individually timed. Reclose interval
timing cannot proceed until the following two conditions are met:
•
The trip condition has gone away.
•
The recloser has opened.
At the end of a reclose interval, an auto reclose attempt is made.
The number of available
Reclose interval
settings corresponds to the highest set
Operations to lockout
(No.
15, 16, or 17) setting.
For example, if the highest set
Operations to lockout
setting is
Operations to lockout - phase
(No. 15) = 4,
then settings
Reclose interval 1
,
Reclose interval 2
, and
Reclose interval 3
are available (three reclose
attempts). Because it is not available,
Reclose interval 4
is hidden and set to zero (0).
The number of reclosing attempts (i.e., available
Reclose interval
settings) is always one less than the number
of trip operations (e.g., 4 “trips” - 1 = 3 “reclosures”).
•
All the
Reclose interval
settings are hidden and set to zero (0) if none of the
Operations to lockout
(No.
15, 16, or 17) settings are set greater than 1 (reclosing is disabled; 1 “trip” - 1 = 0 “reclosures”).
•
If a
Reclose interval
setting is set to zero (0), the corresponding auto reclose attempt and any following
auto reclose attempts are aborted.
•
Note:
Reclose intervals should not be set less than 30 cycles, otherwise the control will got to lockout
prematurely.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......