7-2
Inputs, Outputs, Timers, and Other Control Logic
Date Code 990215
SEL-351P Manual Técnico
Figure SECTION 7: .1:
Example Operation of Optoisolated Inputs IN101 Through
IN106
Input Debounce Timers
Each input has settable pickup/dropout timers (IN101D through IN106D) for input
energization/deenergization debounce. Note that a given time setting (e.g., IN101D = 0.50) is
applied to both the pickup and dropout time for the corresponding input.
Time settings IN101D through IN106D are settable from 0.00 to 1.00 cycles. The SEL-351P
takes the entered time setting and internally runs the timer at the nearest 1/16-cycle. For
example, if setting IN5D = 0.80, internally the timer runs at the nearest 1/16-cycle: 13/16-cycles
(13/16 = 0.8125).
For most applications, the input pickup/dropout debounce timers should be set in 1/4-cycle
increments. For example, in the factory default settings, all the optoisolated input
pickup/dropout debounce timers are set at 1/2-cycle (e.g., IN104D = 0.50). See
SHO Command
(Show/View Settings)
in
Section 10: Serial Port Communications and Commands
for a list of
the factory default settings.
Only a few applications (e.g., communications-assisted tripping schemes) might require input
pickup/dropout debounce timers set less than 1/4-cycle [e.g., if setting IN105D = 0.13, internally
the timer runs at the nearest 1/16-cycle: 2/16-cycles (2/16 = 0.1250)].
The relay processing interval is 1/4-cycle, so Relay Word bits IN101 through IN106 are updated
every 1/4-cycle. The optoisolated input status may have made it through the pickup/dropout
debounce timer (for settings less than 1/4-cycle) because these timers run each 1/16-cycle, but
Relay Word bits IN101 through IN106 are updated every 1/4-cycle.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......