G-4 Setting
SEL
OGIC
®
Control Equations
Date Code 990430
SEL-351P Manual Técnico
Operators in a SEL
OGIC
Control Equation setting are processed in the order shown in
SEL
OGIC
Control Equation Parentheses Operator ( )
More than one set of parentheses ( ) can be used in a SEL
OGIC
Control Equation setting. For
example, the following SEL
OGIC
Control Equation setting has two sets of parentheses:
SV7 = (SV7+IN101)*(50P1+50N1)
In the above example, the logic within the parentheses is processed first and then the two
parentheses resultants are ANDed together. The above example is from Figure 7.25 in
Section 7:
Inputs, Outputs, Timers, and Other Control Logic
. Parentheses cannot be “nested”
(parentheses within parentheses) in a SEL
OGIC
Control Equation setting.
SEL
OGIC
Control Equation NOT Operator !
The NOT operator ! is applied to a single Relay Word bit and also to multiple elements (within
parentheses). Following are examples of both.
Example of NOT Operator ! Applied to Single Element
The internal circuit breaker status logic in the
SEL-
351P operates on 52a circuit breaker auxiliary
contact logic. The SEL
OGIC
Control Equation circuit breaker status setting is labeled 52A. See
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
and
Close
Logic
in
Section 6: Close and Reclose Logic
for more information on SEL
OGIC
Control
Equation circuit breaker status setting 52A.
When a circuit breaker is closed, the 52a circuit breaker auxiliary contact is closed. When a
circuit breaker is open, the 52a contact is open.
The opposite is true for a 52b circuit breaker auxiliary contact. When a circuit breaker is closed,
the 52b circuit breaker auxiliary contact is open. When the circuit breaker is open, the 52b
contact is closed.
If a 52a contact is connected to optoisolated input IN101, the SEL
OGIC
Control Equation circuit
breaker status setting 52A is set:
52A = IN101
Conversely, if a 52b contact is connected to optoisolated input IN1, the SEL
OGIC
Control
Equation circuit breaker status setting 52A is set:
52A = !IN101
[=NOT(IN101)]
With a 52b contact connected, if the circuit breaker is closed, the 52b contact is open and input
IN1 is deenergized [IN1 = 0 (logical 0)]:
52A = !IN101 = NOT(IN101) = NOT(0) = 1
Thus, the SEL
OGIC
Control Equation circuit breaker status setting 52A sees a closed circuit
breaker.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......