Additional Installation Details
2-1
SEL-351P Manual Técnico
SECTION 2: ADDITIONAL INSTALLATION DETAILS
I
NTRODUCTION
This section describes additional SEL-351P Recloser Control installation details not covered in
the
Installation
section of the
SEL-351P Quick-Start Installation and User’s Guide
. Refer also
to Figure 6 in the guide.
O
UTPUT
C
ONTACT
J
UMPERS
Table SECTION 2: .1 shows the correspondence between output contact jumpers and the output
contacts they control. Figure 6 in the
Communications
section of the
SEL-351P Quick-Start
Installation and User’s Guide
shows the exact location and correspondence. With a jumper in
the A position, the corresponding output contact is an “a” type output contact. An “a” type
output contact is open when the output contact coil is deenergized and closed when the output
contact coil is energized. With a jumper in the B position, the corresponding output contact is a
“b” type output contact. A “b” type output contact is closed when the output contact coil is
deenergized and open when the output contact coil is energized. These jumpers are soldered in
place.
In Figure 3 in the
Installation
section of the
SEL-351P Quick-Start Installation and User’s
Guide
, note that the ALARM output contact is a “b” type output contacts and the other output
contacts are all “a” type output contacts. This is how these jumpers are configured in a standard
SEL-351P Recloser Control shipment. Refer to corresponding Figure 7.26 for examples of
output contact operation for different output contact types.
Table SECTION 2: .1: Output Contact Jumpers and Corresponding Output Contacts
Output Contact
Jumpers
Corresponding
Output Contacts
JMP21 - JMP29 (but not JMP23)
ALARM - OUT101
“E
XTRA
A
LARM
” O
UTPUT
C
ONTACT
C
ONTROL
J
UMPER
The SEL-351P has a dedicated alarm output contact (labeled ALARM – see Figure 3 in the
Installation
section of the
SEL-351P Quick-Start Installation and User’s Guide
). Often more
than one alarm output contact is needed for such applications as local or remote annunciation,
backup schemes, etc. An extra alarm output contact can be had without the addition of any
external hardware.
The output contact next to the dedicated ALARM output contact can be converted to operate as
an “extra alarm” output contact by moving a jumper on the main board (see Table SECTION 2:
.2).
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......