Date Code 990430
SEL-351P Command Summary
Page 3 of 3
SEL-351P Manual Técnico
Access
Level B
Commands
Access Level B commands primarily allow you to operate control parameters and output contacts.
All Access Level 1 and Access Level E commands can also be executed from Access Level B.
The screen prompt is: ==>
BRE n
Enter BRE W A to preload breaker/recloser contact wear and trip operation counters. Enter
BRE R to reset breaker/recloser monitor data.
CLO
Close the recloser or circuit breaker.
GRO n
Change active settings group to settings group n (n = 1-6).
OPE
Open the recloser or circuit breaker.
PUL n k
Pulse output contact n (OUT101 - OUT107, ALARM) for k (1-30) seconds. Parameter n must be
specified; k defaults to 1 if not specified.
Access
Level 2
Commands
Access Level 2 commands allow unlimited access to control settings, parameters, and output
contacts. All Access Level 1, Access Level E, and Access Level B commands are available from
Access Level 2. The screen prompt is: =>>
CON n
Control Relay Word bit RBn (Remote Bit n; n = 1 through 8). Execute CON n and the control
responds: CONTROL RBn. Then reply with one of the following:
SRB n
set Remote Bit n (assert RBn).
CRB n
clear Remote Bit n (deassert RBn).
PRB n
pulse Remote Bit n [assert RBn for 1/4 cycle].
COP m n
Copy settings and logic equations from settings group m to settings group n.
LOO Set
M
IRRORED
B
ITS
port to loopback.
PAS
Show existing Access Level 1, E (EZ), B, and 2 passwords.
PAS 1 xxxxxx
Change Access Level 1 password to xxxxxx.
PAS E xxxxxx
Change Access Level E (EZ) password to xxxxxx
PAS B xxxxxx Change Access Level B password to xxxxxx.
PAS 2 xxxxxx
Change Access Level 2 password to xxxxxx.
SET n
Change “regular” settings for settings group n ( n = 1-6).
SET G
Change global settings.
SET L n
Change SEL
OGIC
®
Control Equation settings for settings group n ( n = 1-6).
SET P n
Change port settings for port n (n = 1, 2, 3, F).
SET R
Change Sequential Events Recorder (SER) settings.
SET T
Change text label settings for front-panel display and and extra local control.
STA C
Clears status warning or failure and reboots recloser control.
VER
Show firmware version and options
Key Stroke
Commands
Cntrl - Q
Send XON command to restart communication port output previously halted by XOFF.
Cntrl - S
Send XOFF command to pause communication port output.
Cntrl - X
Send CANCEL command to abort current command and return to current access level prompt.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......