Date Code 990430
Breaker/Recloser Monitor, Battery System Monitor,
8-11
Metering, and Load Profile Functions
SEL-351P Manual Técnico
50% to 100% Breaker Wear
Refer to Figure SECTION 8: .7. The current value changes from 12.0 kA to 1.5 kA. 1.5 kA is
interrupted 3000 times (3000 close/open operations = 6000 - 3000), pushing the breaker
maintenance curve from the 50% wear level to the 100% wear level.
When the breaker maintenance curve reaches 100% for a particular phase, the percentage wear
remains at 100% (even if additional current is interrupted) until reset by the BRE R command
(see
View or Reset Breaker Monitor Information
that follows later). But the current and trip
counts continue to be accumulated until reset by the BRE R command.
Additionally, logic outputs assert for alarm or other control applications – see the following
discussion.
Breaker Monitor Output
When the breaker maintenance curve for a particular phase (A, B, or C) reaches the 100% wear
level (see Figure SECTION 8: .7), a corresponding Relay Word bit (BCWA, BCWB, or BCWC)
asserts.
Relay Word bit Definition
BCWA
Phase A breaker contact wear has reached the 100% wear level
BCWB
Phase B breaker contact wear has reached the 100% wear level
BCWC
Phase C breaker contact wear has reached the 100% wear level
BCW
BCWA + BCWB + BCWC
Example Applications
These logic outputs can be used to alarm:
OUT105 = BCW
or drive the relay to lockout the next time the relay trips:
79DTL = … + TRIP * BCW
View or Reset Breaker Monitor Information – Including Trip Operation Counters
Accumulated breaker wear/operations data are retained if the relay loses power or the breaker
monitor is disabled (setting EBMON = N). The accumulated data can only be reset if the BRE R
command is executed (see the following discussion on the BRE R command).
Via Serial Port
See
BRE Command (Breaker Monitor Data)
in
Section 10: Serial Port Communications and
Commands
. The BRE A command displays the following information:
•
Accumulated number of recloser control initiated trips
•
Accumulated interrupted current from recloser control initiated trips
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......