2-8
Additional Installation Details
Date Code 990215
SEL-351P Manual Técnico
Undervoltage Block for Frequency Elements
If the three-phase voltage is not 120 Vac nominal (phase-to-neutral), then the factory-set pickup
setting 27B81P = 80 may have to be changed. 27B81P is the pickup setting for the undervoltage
block for frequency elements (see Figure 3.27).
Installation with Separate 120 Vac Power, Three-Phase, and Synchronism Check Voltage
See Figure SECTION 2: .3. This installation is similar to the preceding subsection
Installation
with Separate 120 Vac Power and Three-Phase Voltage
(Figure SECTION 2: .2), with the
addition of a load-side voltage to the synchronism check voltage input VS. No voltage input is in
parallel with the incoming 120 Vac power (no extra voltage input is available).
Front-Panel AC SUPPLY LED
No voltage input provides direct indication of incoming 120 Vac power via the front-panel AC
SUPPLY LED (SEL
OGIC
setting LED11). All three voltage inputs VA, VB, and VC are
connected and can provide indirect, but phase-specific monitoring of incoming 120 Vac power.
If the 120 Vac power comes from phase A, keep the factory setting LED11 = 59A1. If the 120
Vac power comes from phase B or C, make setting change LED11 = 59B1 or 59C1, respectively
(for voltage input VB or VC, respectively), with the SET L n command (n = setting group
number).
If the three-phase voltage is not 120 Vac nominal (phase-to-neutral), then change factory-set
pickup setting 59P1P = 104 (for voltage elements 59A1, 59B1, and 59C1; 87% of 120 V) to
some percentage (e.g., 87%) of the nominal phase-to-neutral voltage secondary value of the
three-phase voltage, with the SET n command (n = setting group number). Voltage elements
59A1, 59B1, and 59C1 pick up when nominal voltage is applied to voltage inputs VA, VB, and
VC, respectively (see Figure 3.21).
Undervoltage Block for Frequency Elements
If the three-phase voltage is not 120 Vac nominal (phase-to-neutral), then the factory-set pickup
setting 27B81P = 80 may have to be changed. 27B81P is the pickup setting for the undervoltage
block for frequency elements (see Figure 3.27).
Installation with Only Three-Phase Voltage (120 Vac Power Provided by Three-Phase
Voltage)
See Figure SECTION 2: .4. Only three-phase voltage is brought to the SEL-351P. Jumpers
from the 120 Vac power to voltage input VA are installed. The three-phase voltage must be 120
Vac nominal (phase-to-neutral).
Front-Panel AC SUPPLY LED
Voltage input VA provides direct indication of incoming 120 Vac power via the factory-set
front-panel AC SUPPLY LED (SEL
OGIC
setting LED11 = 59A1). Voltage element 59A1 picks
up when nominal 120 Vac is applied to voltage input VA (see Figure 3.21).
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......