Settings
40
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
No.
Setting
Default
Range
Incr.
5
Min. trip - phase
200.00
OFF, 20.00-639.99 Amps primary
0.01
The
Min. trip - phase
setting determines the minimum phase current threshold for overcurrent detection in
primary amps.
The displayed Amps primary setting range for
Min. trip - phase
is calculated by multiplying the effective
Amps secondary range [0.10 to 3.20] by the
CT Ratio
(No. 3) [200.0]:
(0.10 to 3.20)
•
200.0 = 20.00 to 640.00 range (Amps primary)
If the
CT Ratio
setting changes, the displayed Amps primary setting range for
Min. trip - phase
changes
accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear
slightly different than expected (e.g., 639.99 instead of 640.00).
•
WARNING: If
Min. trip - phase
(No. 5)
, Min. trip - ground
(No. 6),
and
Min. trip - SEF
(No. 7)
are all set to OFF, then overcurrent protection and reclosing are disabled.
•
WARNING: If
Min. trip - phase
is set to OFF, then the following settings are all hidden and set to
OFF or N:
Fast curve - phase
(No. 8)
Delay curve - phase
(No. 10)
Operations - phase fast curve
(No. 13)
Operations to lockout - phase
(No. 15)
Complex fast curve - phase
(No. 25)
Complex delay curve - phase
(No. 27)
High current trip - phase
(No. 29)
High current lockout - phase
(No. 31)
No.
Setting
Default
Range
Incr.
6
Min. trip - ground
50.00
OFF, 1.00-639.99 Amps primary
0.01
The
Min. trip - ground
setting determines the minimum ground current threshold for overcurrent detection
in primary amps.
The displayed Amps primary setting range for
Min. trip - ground
is calculated by multiplying the effective
Amps secondary range [0.005 to 3.20] by the
CT Ratio
(No. 3) [200.0]:
(0.005 to 3.20)
•
200.0 = 1.00 to 640.00 range (Amps primary)
If the
CT Ratio
setting changes, the displayed Amps primary setting range for
Min. trip - ground
changes
accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear
slightly different than expected (e.g., 639.99 instead of 640.00).
If
Min. trip - ground
is effectively set <0.1 Amp secondary (e.g., for
CT ratio
[No. 3] = 200.0,
Min. trip -
ground
<20.00 Amps primary), then the corresponding curves flatten out above 1.5 Amps secondary (e.g., for
CT ratio
[No. 3] = 200.0,
Fast curve - ground
[No. 9] and
Delay curve - ground
[No. 11] flatten out above
300 Amps primary).
•
WARNING: If
Min. trip - phase
(No. 5)
, Min. trip - ground
(No. 6),
and
Min. trip - SEF
(No. 7)
are all set to OFF, then overcurrent protection and reclosing are disabled.
•
WARNING: If
Min. trip - ground
is set to OFF, then the following settings are all hidden and set to
OFF or N:
Fast curve - ground
(No. 9)
Delay curve - ground
(No. 11)
Operations - ground fast curve
(No. 14)
Operations to lockout - ground
(No. 16)
Complex fast curve - ground
(No. 26)
Complex delay curve - ground
(No. 28)
High current trip - ground
(No. 30)
High current lockout - ground
(No. 32)
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......