Settings
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
59
No.
Setting
Default
Range
Incr.
35
Ground trip precedence
N
Y/N
Ground trip precedence
= Y:
•
If the ground fault current is above the
Min. trip - ground
(No. 6) level at the time of trip, the
operations to lockout follows
Operations to lockout - ground
(No. 16).
•
If ground fault current is below the
Min. trip - ground
(No. 6) level and phase fault current is above
the
Min. trip - phase
(No. 5) level at the time of trip, the determination to go to lockout is controlled
by
Operations to lockout - phase
(No. 15).
Ground trip precedence
= N:
•
If ground fault current is above the
Min. trip - ground
(No. 6) level and phase fault current is below
the
Min. trip - phase
(No. 5) level at the time of trip, the determination to go to lockout is controlled
by
Operations to lockout - ground
(No. 16).
•
If phase fault current is above the
Min. trip - phase
(No. 5) at the time of trip, the determination to
go to lockout is controlled by
Operations to lockout - phase
(No. 15).
•
Note: The
Operations to lockout - SEF
(No. 17) is independent of
Ground trip precedence
.
•
This setting is hidden and set to N if
Operations to lockout - phase
(No. 15) = OFF,
Operations to
lockout - ground
(No. 16) = OFF, or the
Operations to lockout - phase
setting equals (=) the
Operations to lockout - ground
setting.
No.
Setting
Default
Range
Incr.
36 Underfrequency
loadshedding
N Y/N
The
Underfrequency loadshedding
setting enables the underfrequency loadshedding scheme, if set to Y.
•
If
Underfrequency loadshedding
is set to Y, enter the following two settings:
Setting
Default
Range
Incr.
Underfrequency pickup
OFF
OFF, 40.10-65.00 Hz
0.01 Hz
The
Underfrequency pickup
setting determines the frequency threshold for underfrequency
loadshedding.
Setting
Default
Range
Incr.
Underfrequency time delay
6.00
2.00-16000.00 cycles
0.25 cyc.
The
Underfrequency time delay
setting determines the time delay for underfrequency
loadshedding.
No.
Setting
Default
Range
Incr.
37
Demand meter time constant
5
5, 10, 15, 30, 60 minutes
The
Demand meter time constant
setting determines the thermal demand meter response time.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......