Date Code 990215
Serial Port Communications and Commands
10-35
SEL-351P Manual Técnico
STA Command Row and Column Definitions
FID
FID is the firmware identifier string. It identifies the firmware revision.
CID
CID is the recloser control firmware checksum identifier.
BCBFID
BCBFID is the firmware checksum of the battery charger board firmware.
W (Warning) or F (Failure) is appended to the values to indicate an out-of-tolerance condition.
OS
OS = Offset; displays measured dc offset voltages in millivolts for the current and
voltage channels. The MOF (master) status is the dc offset in the A/D circuit
when a grounded input is selected.
PS
PS = Power Supply; displays power supply output voltages in dc volts.
TEMP
Displays the internal relay module temperature in degrees Celsius.
RAM, ROM, CR_RAM (critical RAM), and EEPROM
These results verify the relay module memory component status. The columns
display OK if memory is functioning properly, or FAIL if the memory area has
failed.
A/D
Analog to Digital convert status.
IO_BRD
Extra I/O board status.
SF6
Displays SF6 gas pressure in atmospheres.
BATT
Displays status and mode of the battery charger board:
MODE
Mode that battery charger is in:
•
CHARGE Battery is charged to 90% or more, charging at low charge rate.
•
HICHRG Battery is charged to less than 90%, charging at high charge
rate.
•
DISCHG Battery is discharging but is charged to greater than SLPCAP
setting.
•
DISTST
Battery discharge test at 1 Amp for 6 seconds duration.
•
NOBATT Battery is not present.
•
FAIL
Battery monitor/charger has failed or communications with the
battery monitor/charger are temporarily interrupted.
%CAP
The %CAP column shows battery charge level in percent battery capacity
independent of temperature.
HRS_LFT
The HRS_LFT column shows the amount of time left until the control is put into
sleep mode in hours and minutes when in discharge mode. If the control is in
charge or high charge mode, this column reads “XX:XX”.
5V_PSBC
Voltage level in Vdc of the 5 volt supply on the battery charger board.
12V_AUX
Voltage level in Vdc of the 12 volt auxilliary port supply.
VBAT
Voltage level of the 24 volt battery in Vdc.
IBAT
Charge or discharge current in milliamps dc. If current is discharging, value is
preceded by a minus sign “-”; if current is charging, value is displayed with no
preceding character.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......