SEL-351P Quick-Start Installation and User's Guide (Portuguese)
63
EZ S
ETTINGS
S
HEET
Page
1 of 4
F
OR THE
SEL-351P R
ECLOSER
C
ONTROL
Date
!
WARNING:
Anytime an EZ setting is changed, review all the EZ settings before enabling the new settings. Pay close
attention in circumstances where a setting was once set to OFF or N and then later turned on (enabled) - other related
settings may need to be turned on, though may still be set to OFF or N.
Settings Groups 1 (Main) and 2 (Alternate)
EZ Settings (SET EZ n command; n = 1, 2):
Range:
Incr.:
Settings:
Control Identifier (30 characters)
0-9, A-Z, -, /, ., space
--
Circuit Identifier (30 characters)
0-9, A-Z, -, /, ., space
--
CT Ratio
1.0-6000.0
1
PT Ratio
1.0-10000.0
1
Min. trip - phase
OFF, 20.00-640.00 A primary
0.01
Min. trip - ground
OFF, 1.00-640.00 A primary
0.01
Min. trip - SEF
OFF, 1.00-300.00 A primary
0.01
Fast curve - phase (see Page 4 of 4)
OFF, U1-U5 (US), C1-C5 (IEC)
--
Time dial - phase fast curve
0.50-15.00 (U1-U5),
0.05-1.00 (C1-C5)
0.01
EM reset - phase fast curve
Y/N
--
Fast curve - ground (see Page 4 of 4)
OFF, U1-U5 (US), C1-C5 (IEC)
--
Time dial - ground fast curve
0.50-15.00 (U1-U5),
0.05-1.00 (C1-C5)
0.01
EM reset - ground fast curve
Y/N
--
Delay curve - phase (see Page 4 of 4)
OFF, U1-U5 (US), C1-C5 (IEC)
--
Time dial - phase delay curve
0.50-15.00 (U1-U5),
0.05-1.00 (C1-C5)
0.01
EM reset - phase delay curve
Y/N
--
Delay curve - ground (see Page 4 of 4)
OFF, U1-U5 (US), C1-C5 (IEC)
--
Time dial - ground delay curve
0.50-15.00 (U1-U5),
0.05-1.00 (C1-C5)
0.01
EM reset - ground delay curve
Y/N
--
Time delay - SEF
0-16000.00 cycles
0.25
Operations - phase fast curve
OFF, 1-5
1
Operations - ground fast curve
OFF, 1-5
1
Operations to lockout - phase
OFF, 1-5
1
Operations to lockout - ground
OFF, 1-5
1
Operations to lockout - SEF
OFF, 1-5
1
Reclose interval 1
0-999999.00 cycles
0.25
Reclose interval 2
0-999999.00 cycles
0.25
Reclose interval 3
0-999999.00 cycles
0.25
Reclose interval 4
0-999999.00 cycles
0.25
Ranges given for
CT Ratio = 200.0
}
Don’t set less than
30 cycles, else
premature lockout
results
}
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......