Date Code 990430
Loss-of-Potential, Load Encroachment, and Directional Element Logic
4-9
SEL-351P Manual Técnico
Note that Figure SECTION 4: .5 has extra internal enable 32QE, which is used in the directional
element logic that controls negative-sequence and phase overcurrent elements (see
Figure SECTION 4: .17).
The settings involved with internal enables 32QGE and 32VE in Figure SECTION 4: .5 and
Figure SECTION 4: .6 (e.g., settings a2, k2, a0) are explained in the following subsection
Directional Control Settings
.
The zero-sequence voltage-polarized, neutral-current directional element is a sensitive-earth-fault
(SEF) directional element. If V is in the setting ORDER, and no other internal enable is asserted,
32NE may be asserted as shown in Figure SECTION 4: .7. Neutral current will then be used in
determining fault direction.
Best Choice Ground Directional
™ Logic
Refer to Figure SECTION 4: .4 and Figure SECTION 4: .8.
The internal enables 32QGE and 32VE and setting ORDER are used in the
Best Choice Ground
Directional
logic in Figure SECTION 4: .8. The
Best Choice Ground Directional
logic
determines which directional element should be enabled to operate. The neutral ground and
residual ground overcurrent elements set for directional control are then controlled by this
enabled directional element. If V is in the setting ORDER, and no other internal enable is
asserted, 32NE may be asserted as shown in Figure SECTION 4: .7. Neutral current will then be
used in determining fault direction.
Directional Elements
Refer to Figure SECTION 4: .4, Figure SECTION 4: .9, Figure SECTION 4: .10, and
Figure SECTION 4: .11.
The enable output of
Best Choice Ground Directional
logic in Figure SECTION 4: .8, and the
internal enables in Figure SECTION 4: .5, Figure SECTION 4: .6, and Figure SECTION 4: .7
determine which directional element will run.
Additionally, note that if enable setting ELOP = Y or Y1 and a loss-of-potential condition occurs
(Relay Word bit LOP asserts), the negative-sequence voltage-polarized and zero-sequence
voltage-polarized directional elements are disabled (see Figure SECTION 4: .9,
Figure SECTION 4: .10, and Figure SECTION 4: .11).
Refer to Figure SECTION 4: .1 and accompanying text for more information on loss-of-
potential.
Directional Element Routing
Refer to Figure SECTION 4: .4, Figure SECTION 4: .12, and Figure SECTION 4: .13.
The negative-sequence and zero-sequence polarized, residual-current directional element outputs
are routed to the forward (Relay Word bit 32GF) and reverse (Relay Word bit 32GR) logic points
and then on to the direction forward/reverse logic in Figure SECTION 4: .14.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......