Settings
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
47
No.
Setting
Default
Range
Incr.
22
Reset time for auto reclose
1800.00
0-999999.00 cycles
0.25 cyc.
23
Reset time from lockout
600.00
0-999999.00 cycles
0.25 cyc.
The
Reset time for auto reclose
setting qualifies an auto reclose of the recloser. The
Reset time from
lockout
setting qualifies a manual/remote close of the recloser from the lockout state. Traditionally, the
Reset
time from lockout
setting is set shorter than the
Reset time for auto reclose
setting.
Reset timing is blocked (and the reset timer is reloaded) if any overcurrent elements are picked up. Reset
timing can only proceed if all the overcurrent elements are continually dropped out.
•
Both the
Reset time for auto reclose
and
Reset time from lockout
settings are hidden and set to zero (0)
if none of the
Operations to lockout
(No. 15, 16, or 17) settings are set greater than 1 (reclosing is
disabled; 1 “trip” - 1 = 0 “reclosures”).
No.
Setting
Default
Range
Incr.
24
Close power wait time
300.00
0-16000.00 cycles
0.25 cyc.
The
Close power wait time
setting is a time window that starts timing after a reclose interval times out.
During this time window, the SEL-351P checks the trip and close capacitors connected to it:
•
If the trip and close capacitors are charged, this indicates that the close power for the recloser is present,
and reclosing proceeds.
•
If the trip and close capacitors are not charged, this indicates that the close power for the recloser is not
present and reclosing is stalled. If the trip and close capacitors are not charged throughout the time
window, reclosing is aborted at the end of the time window, and the SEL-351P goes to the lockout state.
The 24 Vdc battery also has to be connected and healthy in order for reclosing to proceed.
•
If
Close power wait time
is set to 0 cycles, then the SEL-351P makes only one check for charged trip and
close capacitors, after a reclose interval times out.
•
This setting is hidden and set to 0 cycles if none of the
Operations to lockout
(No. 15, 16, or 17) settings
are set greater than 1 (reclosing is disabled; 1 “trip” - 1 = 0 “reclosures”).
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......