9-4
Setting the SEL-351P Recloser Control
Date Code 990430
SEL
-
351P Manual Técnico
T
IME
-O
VERCURRENT
C
URVES
The following information describes the curve timing for the curve and time dial settings made
for the time-overcurrent elements (see Figure 3.14 through Figure 3.20). The time-overcurrent
relay curves in Figure SECTION 9: .1 through Figure SECTION 9: .10 conform to IEEE
C37.112-1996 IEEE Standard Inverse-Time Characteristic Equations for Overcurrent Relays.
tp = operating time in seconds
tr = electromechanical induction-disk emulation reset time in seconds (if electromechanical
reset setting is made)
TD = time dial setting
M = applied multiples of pickup current [for operating time (tp), M>1; for reset time (tr), M
≤
1].
U.S. Moderately Inverse Curve: U1
U.S. Inverse Curve: U2
tp = TD*(0.0226 + 0.0104/(M
0.02
- 1))
tp = TD*(0.180 + 5.95/(M
2
- 1))
tr = TD*(1.08/(1 - M
2
))
tr = TD*(5.95/(1 - M
2
))
U.S. Very Inverse Curve: U3
U.S. Extremely Inverse Curve: U4
tp = TD*(0.0963 + 3.88/(M
2
- 1))
tp = TD*(0.0352 + 5.67/(M
2
- 1))
tr = TD*(3.88/(1 - M
2
))
tr = TD*(5.67/(1 - M
2
))
U.S. Short-Time Inverse Curve: U5
tp = TD*(0.00262 + 0.00342/(M
0.02
- 1))
tr = TD*(0.323/(1 - M
2
))
I.E.C. Class A Curve (Standard Inverse): C1
I.E.C. Class B Curve (Very Inverse): C2)
tp = TD*(0.14/(M
0.02
- 1))
tp = TD*(13.5/(M - 1))
tr = TD*(13.5/(1 - M
2
))
tr = TD*(47.3/(1 - M
2
))
I.E.C. Class C Curve (Extremely Inverse): C3
I.E.C. Long-Time Inverse Curve: C4
tp = TD*(80.0/(M
2
- 1))
tp = TD*(120.0/(M - 1))
tr = TD*(80.0/(1 - M
2
))
tr = TD*(120.0/(1 - M))
I.E.C. Short-Time Inverse Curve: C5
tp
=
TD*(0.05/(M
0.04
- 1))
tr = TD*(4.85/(1 - M
2
))
All 38 traditional recloser control response curves are available and shown in Figure 9.11
through Figure 9.20. Each curve has two designations. For example, the bottom curve in
Figure 9.11 has the following two designations:
Older electronic control designation:
A
Newer microprocessor-based control designation
101
Use either designation in making curve settings in the SEL-351P.
See Table 8 and Table 9 and following text in the
Settings
section of the
SEL-351P Quick-Start
Installation and User’s Guide
for more information on available time-overcurrent curves,
including user-programmable curves.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......