Date Code 990430
Breaker/Recloser Monitor, Battery System Monitor,
8-17
Metering, and Load Profile Functions
SEL-351P Manual Técnico
includes provisions to manually perform a battery load test via the front-panel and serial
communication ports. You can obtain vital battery system information from the SEL-351P status
report via the front-panel and serial communication ports.
Automatic Battery Load Test
The SEL-351P automatically load tests the 24 V battery about every 24 hours. An internal
24-hour timer cumulatively times whenever the SEL-351P is in the charge mode (e.g., 120 Vac is
powering the SEL-351P and charging the battery). Even if the battery is fully charged, the SEL-
351P maintains a low-rate charging current, so it is still in the charge mode.
After the 24-hour timer runs out and the SEL-351P is still in the charge mode, a 1-A load is
automatically paralleled with the battery for 5 seconds. If battery voltage drops below 80%
nominal (temperature-compensated voltage level) during this load test, the BATTERY
PROBLEM LED illuminates and stays illuminated until the next battery test is successful. The
“discharge test failure” Relay Word bit
DTFAIL
also asserts. Use DTFAIL in a SEL
OGIC
Control Equation to assert an output contact or perform other control functions, if desired, or set
to generate a row in the SER report.
Battery Load Test via Front Panel
You can initiate a battery load test through the front-panel pushbuttons located just below the
liquid crystal display. Press the OTHER pushbutton; a new screen appears, with “BTT” (battery
test) as one of the choices. Using the secondary function arrow pushbuttons, move the
underscore to BTT. To test the battery, press the secondary function SELECT pushbutton. The
SEL-351P responds with one of the following results:
1.
If the battery monitor/charger has a problem, the following message is displayed:
Battery Charger Board FAILED
The BATTERY PROBLEM LED already would be illuminated for this condition. The
battery load test is not performed.
2.
If the battery is damaged or disconnected so it cannot charge or discharge, the
following message is displayed:
Battery failed or not present
The BATTERY PROBLEM LED already would be illuminated for this condition. The
battery load test is not performed.
3.
If the battery is charging or discharging, the battery load test proceeds, and the
following message is displayed:
Testing Battery
. . . . . OK/FAIL
The periods on the second line appear consecutively at each second of the 5-second load test. At
the end of the test, OK or FAIL is displayed. If the battery fails the 1-A load test (same criterion
as described in the preceding
Automatic Battery Load Test
subsection), the BATTERY
PROBLEM LED illuminates and stays illuminated until a subsequent battery load test is
successful. The “discharge test failure” Relay Word bit
DTFAIL
also asserts. Use DTFAIL in a
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......