Settings
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
57
Setting
Default
Range
Incr.
Restore min. trips - time
limit
OFF
OFF, 0-999999.00 cycles
0.25 cyc.
The
Restore min. trips - time limit
is an option to force current thresholds for overcurrent detection
from temporary cold load pickup values back to regular
Min. trip
(No. 5, 6, or 7) levels. This time
limit is set if the user is concerned about an overcurrent element being desensitized too long in the cold
load inrush scheme (force the threshold back, don’t let it return naturally as described with the
preceding
Loss of load diversity
timer setting).
Restore min. trips - time limit
≠
OFF:
The
Restore min. trips - time limit
starts to time if the recloser is closed and both of the
following are true:
•
The cold load pickup scheme is active for at least one element (see preceding
Cold load
pickup
and
Loss of load diversity
settings).
•
At least one of the following three
Restore min. trip
settings is set to Y.
If the recloser remains closed, the
Restore min. trips - time limit
times out and selected current
thresholds for overcurrent detection (see following three
Restore min. trip
settings) are forced
back to their respective regular
Min. trip
(No. 4, 5, and 6)
levels. The respective fast curves are
also enabled again. The natural return to the regular
Min. trip
levels (described with the
preceding
Loss of load diversity
timer setting) can also occur if the inrush current goes below the
Min. trip
level for at least 15 seconds before
Restore min. trips - time limit
times out.
Restore min. trips - time limit
= OFF:
If the cold load pickup scheme is active, then the current thresholds for overcurrent detection
can only return back to their regular
Min. trip
levels naturally as described with the preceding
Loss of load diversity
timer setting.
•
This setting is hidden and set to OFF if
Cold load pickup scheme
is set to N.
Setting
Default
Range
Incr.
Restore min. trip - phase
N
Y/N
Restore min. trip - phase
= Y:
If the cold load pickup scheme is active, the phase current threshold for overcurrent detection is
forced back to the regular
Min. trip - phase
(No. 5) level when the preceding
Restore min.
trips - time limit
times out.
Restore min. trip - phase
= N:
If the cold load pickup scheme is active, the phase current threshold for overcurrent detection
can only return back to its regular
Min. trip - phase
level naturally as described with the
preceding
Loss of load diversity
timer setting.
•
This setting is hidden and set to N if
Restore min. trips - time limit
is set to OFF or
Delay curve
- phase
(No. 10) is set to OFF.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......