Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Date Code 990430
SEL-351P Manual Técnico
Figure SECTION 3: .13:
Levels 5 through 6 Negative-Sequence Instantaneous
Overcurrent Elements
T
IME
-O
VERCURRENT
E
LEMENTS
Phase Time-Overcurrent Elements
Two phase time-overcurrent elements, 51P1T and 51P2T, are available. The elements are
enabled with the E51P enable setting as follows:
Table SECTION 3: .1: Available Phase Time-Overcurrent Elements
Time-Overcurrent
Element
Enabled with
Setting
Operating Current
See Figure
51P1T
51P2T
E51P = 1 or 2
E51P = 2
I
P
, maximum of A-, B-, and
C-phase currents
The following is an example of 51P1T element operation. 51P2T is similar.
Settings Ranges
Besides the settings involved with the Torque Control Switch operation in Figure SECTION 3:
.14 and Figure SECTION 3: .15, the 51P1T and 51P2T phase time-overcurrent elements have
the following settings:
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......