F-2
Setting Negative-Sequence Overcurrent Elements
Date Code 990215
SEL-351P Manual Técnico
To avoid having negative-sequence time-overcurrent element 51QT with such low time-dial
settings trip for this transient negative-sequence current condition, make corresponding minimum
response time setting:
51QMR = 1.50 cycles
(minimum response time; transient condition lasts
less than 1.5 cycles)
Figure APPENDIX F: .1:
Minimum Response Time Added to a
Negative-Sequence Time-Overcurrent Element 51QT
Continue reading in
Coordinating Negative-Sequence Overcurrent Elements
in this appendix
for guidelines on coordinating negative-sequence time-overcurrent elements and a following
coordination example.
C
OORDINATING
N
EGATIVE
-S
EQUENCE
O
VERCURRENT
E
LEMENTS
The following coordination guidelines and example assume that the negative-sequence
overcurrent elements operate on 3I
2
magnitude negative-sequence current and that the power
system is radial. The negative-sequence overcurrent elements in the SEL
-
351P Recloser Control
operate on 3I
2
magnitude negative-sequence current.
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......