Specifications
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
75
Time-Code Input
Relay module accepts demodulated IRIG-B time-code input at Port 1 and Port 2
(Port 1 is an optional EIA-485 port). Do not connect the time-code input into both
Port 1 and Port 2 at the same time. Relay time is synchronized to within
±
5 ms of
time-source input.
Serial
Communications
Two side-panel and one front-panel EIA-232 serial communications ports.
One optional side panel EIA-485 serial port with 2100 Vdc of isolation.
Per-port baud rate selections: 300, 1200, 2400, 4800, 9600, 19200, 38400.
Routine Dielectric
Test
Control ac power: 2500 Vac for 10 seconds.
Optoisolated inputs, analog inputs, and output contacts except Trip and Close:
3100 Vdc for 10 seconds.
Operating Temp.
Relay module:
-40
°
to +85
°
C (-40
°
to +185
°
F)
[LCD contrast impaired for temps. below -20
°
C (-4
°
F)]
Environment
IEC 68-2-30 - 1980 Basic environmental testing procedures, Part 2: Test - Tests
Ca; Damp heat, cyclic
. Severity Level: (12 + 12-hr cycle).
IEC 529 - 1989 Degrees of protection provided by enclosures -
IP32/NEMA 3R
(type test).
RFI and
Interference Tests
ANSI/IEEE C37.60.6.14 - 1981 Control Elements SWC tests for automatic circuit
reclosers and fault interrupters for AC systems, Oscillatory Surge Test method,
6.14.1, applied to control element connections to external devices
, 1.0 to 1.5 MHz
oscillatory test wave of crest voltage of 2.5 - 3.0 kV occurring in the first half-
cycle, decaying to 50% in not less than 6
μ
s.
IEEE C37.90.1 - 1989 IEEE SWC Tests for Protective Relays and Relay Systems
(3 kV oscillatory, 5 kV fast transient) (type test).
IEEE C37.90.2 - 1987 IEEE Trial-Use Standard, Withstand Capability of Relay
Systems to Radiated Electromagnetic Interference from Transceivers,
10 V/m
(type test with enclosure door open).
Exceptions:
5.5.2(2) Performed with 200 frequency steps per octave.
5.5.3
Digital Equipment Modulation Test not performed.
5.5.4
Test signal turned off between frequency steps to simulate
keying.
IEC 801-4 - 1988 Electromagnetic compatibility for industrial-process
measurement and control equipment, Part 4: Electrical fast transient/burst
requirements
, Severity Level: 4 (4 kV on optional power supply, 2 kV on inputs
and outputs) (type test).
IEC 255-22-1 - 1988 Electrical disturbance tests for measuring relays and
protection equipment, Part 1: 1 MHz burst disturbance tests.
Severity Level 3
(2.5 kV common mode, 1.0 kV differential) (type test).
IEC 255-22-3 - 1989 Electrical relays, Section 3: Radiated electromagnetic field
disturbance tests
,
Severity Level: 3 (10 V/m) (type test).
IEC 255-22-4 - 1992 Electrical disturbance tests for measuring relays and
protection equipment, Section 4: Fast transient disturbance test
(type test).
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......