6-22
Close and Reclose Logic
Date Code 990215
SEL-351P Manual Técnico
Three open intervals are also set in the factory settings, resulting in last shot = 3. Any time the
SEL-351P is in the lockout state (Relay Word bit 79LO = logical 1), the SEL-351P is driven to
last shot (if the shot counter is not already at a shot value greater than or equal to shot = 3):
79DLS = 79LO = logical 1
Other Settings Considerations
If no special drive-to-lockout or drive-to-last shot conditions are desired, make the following
settings:
79DTL =
0
(numeral
0)
79DLS =
0
(numeral
0)
With settings 79DTL and 79DLS inoperative, the relay still goes to the Lockout State (and to last
shot) if an entire automatic reclose sequence is unsuccessful.
Overall, settings 79DTL or 79DLS are needed to take the relay to the Lockout State (or to last
shot) for immediate circumstances.
Skip Shot and Stall Open Interval Timing Settings (79SKP and 79STL, respectively)
The skip shot setting 79SKP causes a reclose shot to be skipped. Thus, an open interval time is
skipped, and the next open interval time is used instead.
If 79SKP = logical 1 at the instant of successful reclose initiation (see preceding discussion on
settings 79RI and 79RIS), the relay increments the shot counter to the next shot and then loads
the open interval time corresponding to the new shot (see Table SECTION 6: .3). If the new
shot is the “last shot,” no open interval timing takes place, and the relay goes to the Lockout
State if the circuit breaker is open (see
Lockout State
earlier in this subsection).
After successful reclose initiation, open interval timing does not start until allowed by the stall
open interval timing setting 79STL. If 79STL = logical 1, open interval timing is stalled. If
79STL = logical 0, open interval timing can proceed.
If an open interval time has not yet started timing (79STL = logical 1 still), the 79SKP setting is
still processed. In such conditions (open interval timing has not yet started timing), if
79SKP = logical 1, the relay increments the shot counter to the next shot and then loads the open
interval time corresponding to the new shot (see Table SECTION 6: .3). If the new shot turns
out to be the “last shot,” no open interval timing takes place, and the relay goes to the Lockout
State if the circuit breaker is open (see
Lockout State
earlier in this subsection).
If the relay is in the middle of timing on an open interval and 79STL changes state to 79STL =
logical 1, open interval timing stops where it is. If 79STL changes state back to 79STL =
logical 0, open interval timing resumes where it left off. Use the OPTMN Relay Word bit to
monitor open interval timing (see
Monitoring Open Interval and Reset Timing
earlier in this
subsection).
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......