Date Code 990215
Inputs, Outputs, Timers, and Other Control Logic
7-23
SEL-351P Manual Técnico
The function of the SEL
OGIC
Control Equations in Table SECTION 7: .5 becomes more
apparent in the following example scenario.
Start Out in Setting Group 1
Refer to Figure SECTION 7: .20.
The relay has been in setting Group 1 for some time, with timer logic output SV8T asserted to
logical 1, thus enabling SEL
OGIC
Control Equation setting SS4 for the assertion of input IN105.
Switch to Setting Group 4
Refer to Figure SECTION 7: .20.
The SCADA contact pulses input IN105, and the active setting group changes to setting Group 4
after qualifying time setting TGR (perhaps set at a cycle or so to qualify the assertion of setting
SS4). Optoisolated input IN105 also has its own built-in debounce timer (IN105D) available (see
Figure SECTION 7: .1).
Note that Figure SECTION 7: .20 shows both setting Group 1 and setting Group 4 settings. The
setting Group 1 settings (top of Figure SECTION 7: .20) are enabled only when setting Group 1
is the active setting group and likewise for the setting Group 4 settings at the bottom of the
figure.
Setting Group 4 is now the active setting group, and Relay Word bit SG4 asserts to logical 1.
After the relay has been in setting Group 4 for a time period equal to SV8PU, the timer logic
output SV8T asserts to logical 1, thus enabling SEL
OGIC
Control Equation setting SS1 for a new
assertion of input IN105.
Note that input IN105 is still asserted as setting Group 4 is activated. Pickup time SV8PU keeps
the continued assertion of input IN105 from causing the active setting group to revert back again
to setting Group 1 for a single assertion of input IN105. This keeps the active setting group from
being changed at a time interval less than time SV8PU.
Switch Back to Setting Group 1
Refer to Figure SECTION 7: .20.
The SCADA contact pulses input IN105 a second time, and the active setting group changes back
to setting Group 1 after qualifying time setting TGR (perhaps set at a cycle or so to qualify the
assertion of setting SS1). Optoisolated input IN105 also has its own built-in debounce timer
(IN105D) available (see Figure SECTION 7: .1).
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......