G-8 Setting
SEL
OGIC
®
Control Equations
Date Code 990430
SEL-351P Manual Técnico
only effective input into logic gate OR-1 in Figure 5.1 is SEL
OGIC
Control Equation trip setting
TR.
TR
= 51P1T+51G1T+50P1*SH0 (fuse saving example)
TRCOMM = 0
(not used – set directly to logical 0)
TRSOTF = 0
(not used – set directly to logical 0)
ULTR
= !(51P1 + 51G1)
(discussed in preceding subsection)
Analysis of SEL
OGIC
Control Equation Trip Setting TR
Again, the example trip equation is:
TR = 51P1T+51G1T+50P1*SH0
The Relay Word bit definitions are:
51P1T phase time-overcurrent element timed out
51G1T residual ground time-overcurrent element timed out
50P1
phase instantaneous overcurrent element asserted
SH0
reclosing relay shot counter at shot = 0
In the trip equation, the AND operator * is executed before the OR ope,
Table APPENDIX G: .1:
50P1*SH0
Element 50P1 can only cause a trip if the reclosing relay shot counter is at shot = 0. When the
reclosing relay shot counter is at shot = 0 (see Table 6.3), Relay Word bit SH0 is in the following
state:
SH0 = 1
(logical 1)
If maximum phase current is above the phase instantaneous overcurrent element pickup setting
50P1P (see Figure 3.1), Relay Word bit 50P1 is in the following state:
50P1 = 1
(logical 1)
With SH0 = 1 and 50P1 = 1, the ANDed combination results in:
50P1*SH0 = 1*1 = 1
(logical 1)
and an instantaneous trip results. This logic is commonly used in fuse saving schemes for
distribution feeders.
If the reclosing relay shot counter advances to shot = 1 for the reclose that follows the trip, Relay
Word bit SH0 is in the following state:
SH0 = 0
(logical 0)
If maximum phase current is above the phase instantaneous overcurrent element pickup setting
50P1P for the reoccurring fault, Relay Word bit 50P1 is in the following state:
50P1 = 1
(logical 1)
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......