Date Code 990215
Close and Reclose Logic
6-3
SEL-351P Manual Técnico
Unlatch Close
If the CLOSE Relay Word bit is asserted at logical 1, it stays asserted at logical 1 until one of the
following occurs:
•
The unlatch close condition asserts (ULCL = logical 1).
•
The circuit breaker closes (52A = logical 1).
•
The reclose initiation condition (79RI) makes a rising edge (logical 0 to logical 1)
transition.
•
Or the Close Failure Timer times out (Relay Word bit CF = 1).
The Close Failure Timer is inoperative if setting CFD = OFF.
Factory Settings Example
The factory settings for the close logic SEL
OGIC
Control Equation settings are:
52A =
WB52A
CL
= (PB8 * LT4 + CC) * LT7 * TRCAP * CLCAP
ULCL
= TRIP + WBTR + ! (LT7 + WBCL) + ! (LT4 + WBCL + CC + 79CY)
The factory setting for the Close Failure Timer setting is:
CFD =
15.00
cycles
With setting CFD = 15.00 cycles, once the CLOSE Relay Word bit asserts, it remains asserted at
logical 1 no longer than a maximum of 15 cycles. If the Close Failure Timer times out, Relay
Word bit CF asserts to logical 1, forcing the CLOSE Relay Word bit to logical 0 (and the
reclosing relay to lockout if it was an auto-reclosure).
Note:
There is no need to set CFD to other than 15 cycles. The final trip/close logic in Figure
7.29 takes care of all timing issues concerning the dedicated close output contact. The
CLOSE Relay Word bit output of the close logic in Figure SECTION 6: .1 (that
precedes the CFD timer) propagates to the final trip/close logic in Figure 7.29.
Defeat the Close Logic
If SEL
OGIC
Control Equation circuit breaker auxiliary setting 52A is set with numeral 0
(52A = 0), then the close logic is inoperable. Also, the reclosing relay is defeated (see
Reclosing
Relay
later in this section).
Circuit Breaker Status
Refer to the bottom of Figure 6.1. Note that SEL
OGIC
Control Equation setting 52A (circuit
breaker status) is available as Relay Word bit 52A. This makes for convenience in setting other
SEL
OGIC
Control Equations. For example, if the following setting is made:
52A = IN101
(52a auxiliary contact wired to input IN101)
or
52A = !IN101
(52b auxiliary contact wired to input IN101)
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......