Date Code 990215
Trip and Target Logic
5-19
SEL-351P Manual Técnico
DCUB2
directional comparison unblocking scheme for three-terminal line
(communications from two remote terminals)
The DCUB logic in Figure SECTION 5: .10 takes in the loss-of-guard and permissive trip
outputs from the communication receivers (see Figure SECTION 5: .12 and Figure SECTION 5:
.13) and makes permissive (PTRX1/PTRX2) and unblocking block (UBB1/UBB2) logic output
decisions.
DCUB schemes are typically implemented with FSK (frequency shift carrier) or analog
microwave as the communications medium.
Use Existing SEL-321 Relay DCUB Application Guide for the SEL-351P Recloser Control
Use the existing SEL-321 Relay DCUB application guide (AG96-19) to help set up the SEL-
351P in a DCUB scheme (see preceding subsection
Communications-Assisted Trip Logic -
General Overview
for more setting comparison information on the SEL-321/SEL-351Ps).
External Inputs
See
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for
more information on optoisolated inputs.
PT1, PT2 – Received Permissive Trip Signal(s)
In two-terminal line DCUB applications (setting ECOMM = DCUB1), a permissive trip signal is
received from one remote terminal. One optoisolated input on the SEL-351P (e.g., input IN104)
is driven by a communications equipment receiver output (see Figure SECTION 5: .12). Make
SEL
OGIC
Control Equation setting PT1:
PT1 = IN104
(two-terminal line application)
In three-terminal line DCUB applications (setting ECOMM = DCUB2), permissive trip signals
are received from two remote terminals. Two optoisolated inputs on the SEL-351P (e.g., inputs
IN104 and IN106) are driven by communications equipment receiver outputs (see Figure
SECTION 5: .13). Make SEL
OGIC
Control Equation settings PT1 and PT2 as follows:
PT1 = IN104
(three-terminal line application)
PT2 = IN106
SEL
OGIC
Control Equation settings PT1 and PT2 are routed into the DCUB logic in Figure
SECTION 5: .10 for “unblocking block” and “permissive trip receive” logic decisions.
As explained in the preceding POTT subsection, the SEL
OGIC
Control Equation settings PT1 and
PT2 in Figure SECTION 5: .5 are routed in various combinations to control Relay Word bit PT,
depending on enable setting ECOMM = DCUB1 or DCUB2. Relay Word bit PT is then an input
into the POTT logic in Figure SECTION 5: .6 (for echo keying).
LOG1, LOG2 – Loss-of-Guard Signal(s)
In two-terminal line DCUB applications (setting ECOMM = DCUB1), a loss-of-guard signal is
received from one remote terminal. One optoisolated input on the SEL-351P (e.g., input IN105)
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......