Date Code 990430
Breaker/Recloser Monitor, Battery System Monitor,
8-1
Metering, and Load Profile Functions
SEL-351P Manual Técnico
SECTION 8: BREAKER/RECLOSER MONITOR, BATTERY
SYSTEM MONITOR, METERING, AND LOAD
PROFILE FUNCTIONS
I
NTRODUCTION
The SEL-351P Recloser Control monitoring functions include:
•
Breaker/Recloser Contact Wear Monitor
•
Battery System Monitor
In addition to instantaneous metering, the SEL-351P metering functions include:
•
Demand Metering
•
Energy Metering
•
Maximum/Minimum Metering
This section explains these functions in detail.
B
REAKER
/R
ECLOSER
C
ONTACT
W
EAR
M
ONITOR
The breaker/recloser contact wear monitor in the SEL-351P provides information that helps in
scheduling circuit breaker or recloser maintenance. This monitoring function accumulates the
number of internal and external trip operations and integrates the number of close-open
operations and the per-phase current during each opening operation. The SEL-351P compares
the integrated close-open information to a pre-defined breaker or recloser maintenance curve to
calculate the percent contact wear on a per-pole basis. The SEL-351P updates and stores the
contact wear information, and the number of trip operations, in non-volatile memory. You can
view this information through the front-panel display and by communicating with the SEL-351P
through any serial communication port with a computer.
Individual phase Breaker Contact Wear bits, BCWA, BCWB, and BCWC, assert when the
contact wear percentage on their respective phases reaches 100%. You can use these individual
phase elements or the combined result of these elements, BCW (asserts when BCWA or BCWB
or BCWC assert), in a SEL
OGIC
®
Control Equation to alarm or control other functions, such as
block reclosing.
Enable the breaker/recloser contact wear monitor with the global EZ setting
Recloser Wear
Monitor (AUTO, Y, N)
. Access this setting with the SET FZ (global EZ settings) command from
Access Level E (EZ) or Access Level 2. The contact wear monitor is configured as follows:
•
Recloser Wear Monitor (AUTO, Y, N)
= N
disables the contact wear monitor. Setting
EBMON in Table SECTION 8: .1 is automatically set EBMON = N and the rest of the
settings in Table SECTION 8: .1 are hidden.
•
Recloser Wear Monitor (AUTO, Y, N)
= Y
enables the contact wear monitor. Setting
EBMON in Table SECTION 8: .1 is automatically set EBMON = Y, but you must then
use the
SET G
command (global settings) in Access Level 2 to enter the rest of the
Содержание SEL-351P
Страница 6: ......
Страница 92: ......
Страница 96: ......
Страница 154: ......
Страница 156: ......
Страница 222: ......
Страница 258: ......
Страница 262: ......
Страница 278: ...5 16 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 6 POTT Logic ...
Страница 284: ...5 22 Trip and Target Logic Date Code 990215 SEL 351P Manual Técnico Figure SECTION 5 10 DCUB Logic ...
Страница 324: ......
Страница 368: ......
Страница 406: ......
Страница 482: ......
Страница 534: ......
Страница 539: ......
Страница 549: ......
Страница 551: ......
Страница 587: ......
Страница 597: ......
Страница 601: ......
Страница 603: ......
Страница 609: ......
Страница 621: ......
Страница 635: ......
Страница 649: ......
Страница 663: ...H 14 Distributed Network Protocol DNP V3 00 Date Code 991201 SEL 351P Manual Técnico Enter the new DNP Binary map CR ...
Страница 665: ......
Страница 671: ......