82
FA.18
Detection factor of
output
current
imbalance
1.00
~
10.00 1.00
:
imbalance
detection is disabled
Note
:
detection of output
current imbalance and output
phase loss share the same
reference parameter FA.17 and
fault code E-13.
—
1.00
×
FA.19
reserved
—
—
0
◆
FA.20
PID
feedback
disconnection
processing
0
:
disabled
1
:
alarm and maintain the
operation at the frequency of
disconnection moment
2
:
protection action and coast to
stop
3
:
alarm and decelerate to
zero-speed operation according
to preset mode
1
0
×
FA.21
Feedback
disconnection
detection value
0.0
~
100.0%
0.1%
0.0%
○
FA.22
Feedback
disconnection
detection time
0.0
~
3600.0S
0.1S
10.0
○
FA.23
reserved
—
—
0
◆