112
2: 0.1s
This function code defines dimension of Acc/Dec time.
F1.20
Frequency setting of forward jog operation
0.00
~【
F0.16
】
upper limit freq.
5.00
F1.21
Frequency setting of reverse jog operation
0.00
~【
F0.16
】
upper limit freq.
5.00
F1.22
Jog Acc time
0.1
~
3600.0s
Depending
on model
F1.23
Jog Dec time
0.1
~
3600.0s
Depending
on model
F1.24
jog interval time
0.1
~
100.0s
0.1
F1.20~F1.24 defines relevant parameters of jog running. As showed in figure F1-5, t1 and t3 are accelerating time and
decelerating time respectively of actual running; t2 is jog time; t4 is jog interval time (F1.24); f1 is forward jog running
frequency (F1.20); f2 is reverse jog running frequency (F1.21). The jog accelerating time of actual running t1 is
determined by the following formula:
t1=F1.20*F1.22/F0.15
The jog decelerating time of actual running t3 is defined as follows:
t3=F1.21*F1.23/F0.15
F0.15 is the maximum output frequency.