193
0.00Hz
~
upper limit
10.00
F9.61
Preset traverse frequency hold time
0.0
~
3600.0s
0.0
These above function codes defined run frequency before entering traverse mode or when exiting traverse mode and
hold time of the frequency. If F9.61≠0, the driver will run at preset traverse frequency when start, and enter traverse
mode after preset traverse frequency hold time.
F9.62
Traverse amplitude
0.0
~
100.0
%
(of reference freq.
)
0.0%
Reference value of traverse amplitude is determined by F9.57. If F9.57=0, traverse amplitude AW=max.frequency*F9.62;
if F9.57=1, AW=reference*F9.62.
Notice
:
1: the traverse frequency is limited by upper and lower limit of frequency. Improper setting of the frequency limit will
result in faults.
2: the traverse is invalid for jog or PID control mode.
F9.63
Step frequency
0.0
~
50.0
%
(of traverse amplitude)
0.0%
This function code indicates the falling amplitude after reaching upper limit of frequency, or the rising amplitude after
reaching lower limit of frequency.
If it is set at 0.0%, then there will be no step frequency.
F9.64
Traverse rising time
0.1
~
3600.0s
5.0