When undedrvoltage of DC bus happens during stopping, the LED displays “PoFF”; when it happens during running, if
FA.02=0, the LED displays “PoFF”, if FA.02=1, the LED displays “E-07” and the alarm indicator is on.
21: dormancy state
This signal is sent when the VFD is in dormancy state.
22
:
VFD alarm signal
This signal is sent when the following situation happens: PID disconnection, RS485 communication fail, keypad
communication fail, EEPROM R/W fault, encoder disconnection, etc.
23
:
AI1
>
AI2
This indicator signal is sent when analog input AI1
>
AI2. See F6.05
~
F6.11.
24
:
preset length arrival
This signal is given when the actual length
(
F9.69
)
≥preset length
(
F9.68
)
. The length counting terminal X6 is set as
function of NO.47.
25
:
preset timing time arrival
This signal is give when the actual timing time≥F7.36
(
preset timing time
)
.
26
:
dynamic braking
This signal is sent when the VFD is in dynamic braking action. See FC.00
~
FC.03.
27
:
DC braking action
This signal is sent when the VFD is in DC braking action. See description of function code F1.00
~
F1.12 for
corresponding setting.
28
:
flux braking action
This signal is sent when the VFD is in flux braking action. Refer to function code FC.21 for corresponding setting.
29
:
torque limiting
This signal is sent during torque control. Refer to F4.10
~
F4.23.
30
:
over torque
This indicator signal is sent according to F4.22
~
F4.24 setting.
31
:
auxiliary motor 1