201
In the normal VF mode, FA.06 is used for amplitude limiting during accelerating or constant speed running; in Vector VF
mode, FA.06 is used for amplitude limiting during accelerating, and no such limit process during constant speed running;
in vector mode, the amplitude limit during constant speed running is only related to F4.20
~
F4.21.
FA.07
current limiting in field weakening region
0
~
1
0
0
:
limited by current limiting threshold of FA.06.
When output frequency is within 50Hz, FA.06 is used for amplitude limiting.
1
:
limited based on corrected current from FA.06
When output frequency is above 50Hz, amplitude limiting is processed based on corrected current from FA.06.
FA.08
Current limit factor in accelerating
0
~
100 0
:
current limit of accelerating
invalid
Depending on
model
During accelerating, the larger of this value, the stronger of the overcurrent suppressing ability.
FA.09
Current limit in constant speed running
0
~
1
1
0
:
disabled
1
:
enabled
FA.10
Off load detection time
0.1s
~
60.0s
5.0
FA.11
Off load detection level
0.0
~
100.0%*rated current of VFD
0.0%
0
:
off load detection disabled
Off load detection level (FA.10) defines the current threshold of off load action, and the set value is the percentage