221
FE.03
STOP + RUN emergency stop
0
~
1
1
0
:
disabled
1
:
coast to stop
Press
RUN
and
STOP/RESET
, the driver will coast to stop.
FE.04
Close-loop display factor
0.01
~
100.00
1.00
This function code is used to calibrate the error between the actual parameters (pressure, flow rate, etc.) and preset or
feedback parameters (voltage, current). It has no effect on close-loop regulation.
FE.05
Rotating speed display factor
0.01
~
100.00
1.00
This function code is used to calibrate the error of rotating speed display. It has no effect on the actual speed.
FE.06
Line speed factor
0.01
~
100.00
1.00
This function is used to calibrate the error of line speed display. It has no effect on the actual speed.
FE.07
Encoder regulation speed
1
~
100
70
FE.08
Monitoring parameters selection 1 in operation status
0
~
57
0
FE.09
Monitoring parameters selection 2 in operation status
0
~
57
5
The items of main monitoring interface can be changed by modifying the set value of the above function codes. For