65
F7.10
Effective logic setting
of input terminal (X1
~
X7)
0
~
7FH
0 is positive logic, i.e. terminal
Xi is enabled when it connects
with common terminal and
disabled if disconnected.
1 is negative logic, i.e. terminal
Xi is disabled when it connects
with common terminal and
enabled when disconnected.
1
00
×
F7.11
FWD/REV
terminal
control mode
0
:
two-wire control mode 1
1
:
two-wire control mode 2
2
:
three-wire control mode 1
3: three-wire control mode 2
1
0
×
F7.12
UP/DOWN
terminal
frequency
modifying
rate
0.01
~
50.00Hz/S
0.01Hz/S
1.00
○
F7.13
reserved
—
—
0
◆
F7.14
Y1 output delay time
0.0
~
100.0s
0.1S
0.0
×
F7.15
Y2 output delay time
0.0
~
100.0s
0.1S
0.0
×
F7.16
R1 output delay time
0.0
~
100.0s
0.1S
0.0
×
F7.17
R2 output delay time
(reserved)
0.0
~
100.0s
0.1S
0.0
×