205
0.0
~
3600.0s
10.0
The lasting time before protection action after feedback connection happened.
Fig. FA-4 Closed Loop Feedback Loss Detection
FA.23
reserved
reserved
0
FA.24
Action of RS485 communication error
0
~
2
1
0
:
protection action and coast to stop
1
:
alarm and maintain current operation
2
:
alarm and stop according to set mode
FA.25
RS485 communication timeout detect
0.0
~
100.0s
5.0
If RS485 didn’t receive the right data signal within the defined time by this parameter, the RS 485 communication error is
confirmed and the driver will respond with corresponding action based on FA.24 setting. The RS485 communication