149
2
:
reverse running
(
REV
)
Short-circuit terminal with COM, VFD runs reverse. Valid only when F0.06=1.
3
:
three-wire running control
Refer to function description of running mode 2, 3 (three-wire control mode 1, 2) of F7.11.
4
:
forward jog control
Short-circuit terminal with COM, VFD runs as jog forward. Valid only when F0.06=1.
5
:
reverse jog control
Short-circuit terminal with COM, VFD runs as jog reverse. Valid only when F0.06=1.
6
:
coast to stop
This function is the same with F1.08. Only that it is realized by terminal and convenient for remote control.
7
:
external reset signal input(RST)
If the VFD malfunctions, it can be reset through this terminal. This function is the same with key
STOP/RESET
, and is
valid in any command channel.
8
:
external fault normally-open input
9
:
external fault normally-closed input
The fault signal of external device can be input through this terminal so as to facilitate fault monitoring of external
device. After receiving fault signal of external device, VFD will display “E-19” (external device fault alarm). The fault
signal can be input with two methods of normally open and normally closed.
10
:
emergency stop function
(
brake with fastest speed
)
This function is used in emergency stop condition. The terminal is short-circuited with COM, and the braking will
proceed with emergency standby decreasing time (F1.36).
11
:
reversed
12
:
frequency increase
Terminal is short-circuited with COM, frequency increases. Valid only when frequency setting channel is digital
setting 2 (terminal UP/DOWN adjustment).
13
:
frequency decrease
Terminal is short-circuited with COM, frequency decreases. Valid only when frequency setting channel is digital