213
FC.09
Password of operation limit function
0
~
65535
0
By default, the password is 0, and FC.10 and FC.11 can be set; when there is a password, the setting of FC.10 and FC.11
should be after the password is verified right.
The password can be set at 0 if there is no need for it.
For this password setting, input five-digit number and press
ENTER
,the password will take into effect after one
minute later.
When there is a need to modify the password, choose FC.09 function code, press
ENTER
to enter verification status.
After successful authentication, enter modify status and input the new password, press
ENTER
, and the password is
modified successfully. One minute later, the new password will take into effect automatically. For clear password, just set
it at “00000”.
FC.10
Operation limit function
0
~
1
0
0
:
disabled
1
:
enabled
During operation limit, as long as the total operation time exceeds the time specified by FC.11, the driver will respond
with protection action and coast to stop, and the keypad displays E-26 (RUNLT). To clear this fault, just very FC.09 right
and set FC.10 at “0”(disabled).
FC.11
Limit time
0
~
65535h
0
Note
:
this parameter can be reset, see description of FC.09.
FC.12
Freq. decreasing point of transient power failure