185
command, the driver will run at the preset frequency of the stage for the remaining time of the stage.
Fc.00
PLC restart mode
0
~
2
0
0
:
start from the first stage
The driver restarts from the first stage of PLC after interrupts, such as stop command, fault or poweroff.
1
:
continue from the stage where the driver stops
When the driver stops caused by stop command, fault or poweroff, it can record the time that it has undergone in the
current stage. After restart, it will run at the preset frequency of the stage for the remaining time of the stage, as Fig. F9-4
shows.
Fig. F9-4 PLC Start Mode 1