The VFD runs in process PID control mode in this frequency setting mode. Function codes of F8 group are needed to be
set such as “process PID parameter”, analog given and impulse given. The running frequency of VFD is the value after PID
taking effect. For details check F8 group function description.
9: panel potentiometer setting
Operate the potentiometer on keyboard to adjust running frequency, and regulating range is 0~max. output frequency
【
F0.15
】
.
F0.08
Auxiliary freq. source
B
0
~
9
(
principle freq. channel selection
)
3
0
:
digital set 1(keypad
, encoder)
1
:
digital set 2
(
UP/DOWN terminal adjustment)
2
:
digital set 3
(
communication setting
)
3
:
AI1 analog set
(
0
~
10V/20mA
)
4
:
AI2 analog set
(
0
~
10V
)
5
:
impulse set
(
0
~
50KHZ
)
6
:
simple
PLC
setting
7
:
multispeed running setting
8
:
PID control setting
9
:
panel potentiometer setting
Auxiliary frequency specified channel has the same meaning of each item as principle frequency channel, for details
check F0.07 description.
F0.09
frequency source combinational algorithm
0
~
9
0
0: principle frequency source A
1: A+K*B
Principle frequency A, auxiliary frequency B multiplied by weight coefficient K, the sum of the above two values are the