211
is brake resistor connected, the pumping voltage energy will be released via the brake resistor to achieve drop of DC
voltage. When the DC side voltage falls to a specific value (initial value - brake backlash), the internal brake unit will
close.
Fig. FC-1 Dynamic Braking
FC.04
Restart after power failure
0
~
2
0
0
:
disabled
The driver will not auto restart after power on.
1
:
start at start frequency
After power on, if start condition is met, the driver will auto start at start frequency after a period of time specified by
FC.05.
2
:
start in speed tracking mode
After power on, if start condition is met, the driver will auto start in speed tracking mode after a period of time specified