212
by FC.05.
PC.05
Restart delay after power failure
0.0
~
60.0s
5.0
In this delay time, any command input is invalid. If stop command is input, the driver will auto unlock speed tracking
restart status and back to normal stop status.
Notice:
1
:
FA.02 needs to be set at 0 to ensure the restart after power off is valid.
2
:
this parameter may cause unexpected start of motor and bring damage to equipment and people, be cautious to use
it.
FC.06
Auto reset times
0
~
100
0
FC.07
Auto reset interval
0.1
~
60.0s
3.0
100
:
no times limit, i.e. infinite times
When fault occurs during operation, the driver will stop output and display fault codes. After a period of time specified
by FC.07, the driver will auto reset and restart according to set start mode.
The auto reset times after fault occurring is specified by FC.06. When it is set at 0, auto restart function will be disabled
and the driver can only be reset manually. When FC.06 is set at 100, there will be no limit for reset times.
For IPM fault, external fault, etc., auto reset function of the driver is not allowed.
FC.08
Cooling fan control
0
~
1
0
0
:
auto control mode
1
:
operation all the way during power on