73
F8.19
Delay time of adding
pump
0.0
~
3600.0s
0.1S
10.0
○
F8.20
Delay time of reducing
pump
0.0
~
3600.0s
0.1S
10.0
○
F8.21
Water supply enabling
(F8.21-F8.24
not
supported
by
hardware)
0: disabled
1: PFC enabled
2: SPFC enabled
1
0
×
F8.22
Delay time of terminal
disconnect
and
connect
0.0
~
6000.0s
0.1s
0.1
○
F8.23
Polling time
0.0
~
6000.0s
0.1h
48.0
○
F8.24
Lower limit freq. of
reducing pump
0.0
~
600.00Hz
0.01Hz
35.00
○
F8.25
Sensor range
0.00
~
60.00
(
MPa
、
Kg
)
0.01
10.00
○
F8.26
Pressure setting
0.00
~【
F8.25
】(
MPa
、
Kg
)
0.01
5.00
○
F8.27
Main pump start delay
0.0
~
3600.0s
0.1S
0.3
○
F8.28
Auxiliary pump start
mode selection
0
:
directly
1
:
softly
1
0
×
F8.29
Proportional gain KP2
0.01
~
100.00
0.01
1.00
○
F8.30
Integral time Ti2
0.01
~
10.00s
0.01s
0.10
○
F8.31
Derivative time Td2
0.01
~
10.00s
0.0
:
no derivation
0.01s
0.00
○