46
Reference Manual
00809-0100-4530, Rev DD
May 2016
Verify probe length
Segmented probe ordered with model code 4S
Before installation, verify the probe length (L) on the label. If the probe length needs to be
adjusted, see
“Adjusting the probe length” on page 53
Segmented probe ordered as spare part kit
Before installation, the number of segments that add up to the desired probe length must
be determined. Also, the bottom segment may need to be shortened. See
.
Assemble the segmented probe
Note
If there is enough space beside the tank, the probe can be assembled before inserting it into
the tank.
1.
Insert the stop screw to the top segment. Tighten approximately two turns.
L =
SN:
Probe length
Probe segments box
Top Segment
~
Two turns