Rosemount 5300 Series with HART® to Modbus® Converter
May 2016
Reference Manual
00809-0100-4530, Rev DD
400
Rosemount 5300 Series with HART® to Modbus® Converter
Table J-15. Output Variables for Floating Point Format Code 2
Table J-16. Output Variables for Floating Point Format Code 3
Register Name
Register
Number
Note
Slave 1 Status
2100
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV.
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or other master
present)
Bit 15: HTM Task not running (option not available).
Note:
Bit 1-3 is set when Invalid Measurement of Slave 1
Non PV, i.e. all three bits are set simultaneously.
Slave 1 PV
2102
Primary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 2.
Slave 1 SV
2104
Secondary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 2.
Slave 1 TV
2106
Tertiary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 2.
Slave 1 FV (QV)
2108
Fourth variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 2.
Register Name
Register
Number
Note
Slave 1 Status
2200
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV.
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or other master
present)
Bit 15: HTM Task not running (option not available).
Note:
Bit 1-3 is set when Invalid Measurement of Slave 1
Non PV, i.e. all three bits are set simultaneously.
Slave 1 PV
2202
Primary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 3.
Slave 1 SV
2204
Secondary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 3.
Slave 1 TV
2206
Tertiary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 3.
Slave 1 FV (QV)
2208
Fourth variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 3.
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...